SSG-RP Industrial Ultra-wide Temp UPS, Rackmount 1kVA
Nominal VA: 1000
Electrical Input
Nominal AC Voltage: 120Vac
AC Voltage Range: 80-138Vac
Frequency: 50/60 Hz ± 5% (Auto Tracking)
Power Factor Correction: >0.98 (at full load)
Surge Supression: IEEE/ANSI C62.41
Efficiency (Typ.): 88%
Electrical Output
Watts: 700
AC Voltage: 100, 110, 115 or 120Vac (sine wave)
Frequency: 50/60 Hz (Auto Tracking)
Frequency Stability: ± 0.3% (Battery Mode), ± 5% Synchronized to the input frequency in utility mode
Voltage Regulation: ± 2%
Step Load Change: ± 7% for 100% load variation, recovery in 5ms
Harmonic Distortion: < 3% Linear Load, < 5% Non-Linear Load
Overload: 110% for 40 seconds, 125% for 18 seconds, 150% immediate
Crest Ratio: 3:1
Battery
DC Bus Voltage (nominal): 48Vdc
Battery Pack Type: Hot-Swappable Pack Separate Enclosure from UPS Module, User-Replaceable
Battery Type (Std. Battery Module): 4 or 8 each, wide temperature range (-40°C to 80°C), Maintenance-Free, Sealed VRLA, 12Vdc, 5Ah
Battery Runtimes, Full/Half Load in Minutes: 10 / 16
Recharge Time: 6 Hours to 90%
Transfer Time
Line Falls/Recovers: Zero
UPS to Bypass or Reverse: < 4ms
After Overload: Auto Transfer to UPS
Electrical Connections - For hardwired models, contact us
Input -1: 6' Cord with 5-15P Plug
Input -2: 6' Cord with Schuko Plug
Output -1: (8) 5-15R
Output -2: (4) IEC320 C13 Outlets
Environmental
Temperature - Operational and Storage: -30°C to 65°C (-22°F to 149°F) Note: When operated in temperatures above 25°C, the battery service life will be reduced.
Humidity: 10% to 95% Non - Condensing
Altitude: 10,000 Feet (3,000 meters) without derating
Cooling: Low Velocity Forced Air Fan
Heat Dissipation BTU/Hour: 342
Audible Noise (@ 1 Meter): <50dBA
Controls & Indicators
LED Display: Line, Inverter, Battery, Bypass, Battery %, Load %, Alarm, Charger, Overload
Audible Alarms: DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp., Overload, Fault Alarm
Load Segment Control: Two programmable load segments, one continuous load segment
Remote Emergency Power Off (or): (Standard) Meets NFPA 70, NEC 645-11 (REPO connections located on the UPS rear panel)
Remote Output Receptacle Control: (Optional) UPS Load Segment Controlled Output Receptacles can be turned off and on using a remote isolated switch contact.
Communications: USB Port, RS-232C Serial Port, Optional SNMP/HTTP Agent Board (UPS Bundled UPSilon Software)
Mechanical - For mounting dimensions, contact us
UPS Dimensions H x W x D inches (mm): (2U) 3.5 x 19 x 20.8 (88.9 x 482.6 x 528.3)
SSGR Battery Module: (2U) 3.5 x 19 x 20.2 (88.9 x 482.6 x 513.1)
Weight in lbs (kg): (2U) UPS Module = 31.9 (14.5), SSGH-B Battery Module = 37.4 (17)
Agency Approvals
UL 1778, UL 508, cUL, FCC Class B