SSG Industrial Wide-temp UPS, Rackmount 6kVA
Nominal VA: 6000
Electrical Input
Nominal AC Voltage: 208-240Vac
AC Voltage Range: 176-276Vac
Frequency: 50/60 Hz ± 5% Auto Tracking (45-65Hz)
Power Factor Correction: >0.97 (at full load)
Surge Supression: IEEE/ANSI C62.41
Efficiency (Typ.): 88%
Electrical Output
Watts: 4200
AC Voltage (User Programmable): 208, 220, 230 or 240Vac (sine wave)
Frequency: 50/60 Hz (Auto Tracking)
Frequency Stability: ± 0.3% (Battery Mode), ± 5% Synchronized to the input frequency in utility mode
Voltage Regulation: ± 2%
Step Load Change: ± 7% for 100% load variation, recovery in 5ms
Harmonic Distortion: < 3%
Overload: 110% for 40 seconds, 125% for 18 seconds, 150% immediate
Crest Ratio: 3:1
Battery
DC Bus Voltage (nominal): 192Vdc
Battery Pack Type: User-Replaceable, Hot-Swappable Pack, Separate Enclosure from UPS Module
Battery Type: 12-Year Rated, Maintenance-Free, Sealed VRLA Batteries, 12Vdc, 7Ah
Battery Runtimes, Full/Half Load in Minutes: 5 / 10
Recharge Time: 4 Hours to 90%
Transfer Time
Line Falls/Recovers: Zero
UPS to Bypass or Reverse: < 4ms
After Overload: Auto Transfer to UPS
Electrical Connections - For hardwired models, contact us
Input: Hardwire
Output: Hardwire
Environmental
Temperature - Operational: -20°C to 55°C (-4°F to 131°F) When operated in temperatures above 25°C, the battery service life will be reduced.
Temperature - Storage: -20°C to 55°C (-4°F to 131°F) Batteries stored at 50°C will require monthly recharging and have a reduced service life.
Humidity: 10% to 95% Non - Condensing
Altitude: 10,000 Feet (3,000 meters) without derating
Cooling: Low Velocity Forced Air Fan
Heat Dissipation BTU/Hour: 2457
Audible Noise (@ 1 Meter): <50dBA
Controls & Indicators
LCD Display: MIMIC Graphical Display, Input/Output Voltage, Frequency, Load, Alarm, Programmable settings & UPS state icons
Audible Alarms: DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp., Overload, Fault Alarm
Remote Emergency Power Off: Meets NFPA 70, NEC 645-11 (REPO connections located on the UPS rear panel)
Communications: RS-232C Serial Port, Optional SNMP/HTTP Agent Board (UPS Bundled UPSilon Software)
Mechanical - For mounting dimensions, contact us
UPS Dimensions H x W x D inches (mm): 7 x 19 x 21.8 (177.8 x 482.6 x 553.7)
SSGR Battery Module (each): 3.5 x 19 x 21.3 (88.9 x 482.6 x 541)
Weight in lbs (kg): (4U) UPS Module = 62.5 (28.3)
12-Year VRLA Batteries: 2 Each (2U) External Battery Module = 70.6 (32)
Total System Weight: 203.7 (92.4)
Agency Approvals
UL 1778, UL 508, cUL, CE, FCC Class A