IEC 61850-3 and IEC 62439-3 full Gigabit managed Ethernet switch with 4 100/1000BaseT(X) ports, 6 100/1000Base SFP ports, isolated dual power supply (88 to 300 VDC or 85 to 264 VAC), -40 to 75°C operating temperature
Ethernet Interface
-
100/1000BaseT(X) Ports (RJ45 connector)
-
100/1000BaseSFP Ports
-
Standards
- IEEE 802.3u for 100BaseT(X) and 100BaseFX
IEEE 802.3ab for 1000BaseT(X)
IEEE 802.3z for 1000BaseX
IEEE 802.1D-2004 for Spanning Tree Protocol
IEEE 802.1w for Rapid Spanning Tree Protocol
IEEE 802.1p for Class of Service
IEEE 802.1Q for VLAN Tagging
IEEE 802.1X for authentication
IEEE 802.3ad for Port Trunk with LACP
IEEE 802.3x for flow control
Ethernet Software Features
-
Management
- HTTPS
Dying Gasp
Back Pressure Flow Control
DHCP Option 66/67/82
Fiber check
Flow control
LLDP
Port Mirror
SNMP Inform
BOOTP
DHCP Server/Client
HTTP
IPv4/IPv6
RARP
SMTP
SNMPv1/v2c/v3
Syslog
Telnet
TFTP
-
MIB
- MIB-II
Ethernet-like MIB
Bridge MIB
P-BRIDGE MIB
Q-BRIDGE MIB
RSTP MIB
RMON MIB Groups 1, 2, 3, 9
-
Filter
- IGMP v1/v2/v3
GMRP
GVRP
802.1Q
QinQ VLAN
-
Redundancy Protocols
- Link Aggregation
MSTP
RSTP
STP
Turbo Chain
Turbo Ring
MRP
HSR
PRP
Coupling
RSTP grouping
-
Security
- RADIUS
TACACS+
SSH
Port Lock
Broadcast storm protection
MAB authentication
Sticky MAC
Access control list
-
Time Management
- NTP Server/Client
SNTP
IEEE 1588v2 PTP (hardware-based)
-
Power Substation
- GOOSE Check
IEC 61850 QoS
MMS
Switch Properties
-
Priority Queues
-
Max. No. of VLANs
-
VLAN ID Range
-
RSTP Grouping ID Range
-
IGMP Groups
-
MAC Table Size
-
Packet Buffer Size
Power Parameters
-
Input Voltage
- 110-220 VAC, 110-220 VDC (88 to 300 VDC, 85 to 264 VAC)
-
Input Current
- 0.5 A @ 110-220 VAC
0.3 A @ 110-220 VDC
-
Alarm Contact Channels
- Resistive load: 1 A @ 24 VDC
-
Overload Current Protection
-
Reverse Polarity Protection
Physical Characteristics
-
IP Rating
-
Dimensions (without ears)
- 74 x 148 x 120 mm (2.91 x 5.83 x 4.72 in)
-
Weight
-
Installation
Environmental Limits
-
Operating Temperature
- -40 to 75°C (-40 to 167°F)
-40 to 85°C (-40 to 185°F) for 16 hrs (tested in accordance with IEC 60068-2-2)
-
Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
-
Ambient Relative Humidity
- 5 to 95% (non-condensing)
Standards and Certifications
-
EMC
-
EMI
- CISPR 32, FCC Part 15B Class A
-
EMS
- IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
IEC 61000-4-4 EFT: Power: 4 kV; Signal: 4 kV
IEC 61000-4-5 Surge: Power: 4 kV; Signal: 4 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF
EN 61000-4-11
-
Power Substation
- IEC 61850-3 Edition 2.0 Class 2
IEEE 1613
-
Railway
-
Safety
MTBF
-
Time
-
Standards
- Telcordia (Bellcore) Standard TR/SR