Description
Rugged controller, 1 GHz CPU, 2-port RJ45 Ethernet, IEC 61131-3, -40 to 75°C operating temperature
Computer
-
CPU
- 32-bit Cortex-A8 1 GHz CPU
-
OS
- Real-time Linux (PREEMPT_RT)
-
Clock
- Real-time clock with capacitor backup
Memory
-
eMMC
- 4 GB (1.7 GB reserved for the user)
-
SDRAM
- 512 MB
-
SPI-NVRAM
- 128 KB
-
microSD Slot
- Up to 32 GB (SD 2.0 compatible)
Control Logic
-
Language
- IEC 61131-3
Ethernet Interface
-
10/100BaseT(X) Ports (RJ45 connector)
- RJ45 version: 2, 1 MAC address (Ethernet bypass) or 2 MAC addresses, jumper selectable
-
Magnetic Isolation Protection
- 1.5 kV (built-in)
Ethernet Software Features
-
Configuration Options
- v
-
Industrial Protocols
- Modbus TCP Client (Master), Modbus TCP Server (Slave), Moxa AOPC (Active Tag), SNMPv1/v2c Trap, SNMPv1/v2c/v3
-
Management
- BOOTP, IPv4, SMTP, UDP
-
Security
- SSH
-
Time Management
- SNTP
Serial Interface
-
Console Port
- RS-232 (TxD, RxD, GND), 3-pin (115200, n, 8, 1)
Modbus RTU/ASCII
-
Functions Supported
- 1, 2, 3, 4, 5, 6, 15, 16
-
Mode
- Master, Slave
Modbus TCP
-
Functions Supported
- 1, 2, 3, 4, 5, 6, 15, 16
-
Mode
- Master, Slave
Power Parameters
-
Power Connector
- Spring-type Euroblock terminal
-
No. of Power Inputs
- 2
-
Input Voltage
- 24 to 110 VDC
-
Power Consumption
- 223 mA @ 24 VDC
Physical Characteristics
-
Housing
- Metal
-
Installation
- Wall mounting (with optional kit)
-
Wiring
- Power cable, 14 to 28 AWG
Environmental Limits
-
Operating Temperature
- -40 to 75°C (-40 to 167°F)
-
Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
-
Ambient Relative Humidity
- 5 to 95% (non-condensing)
-
Altitude
- 2000 m
Standards and Certifications
-
EMC
- EN 55032/24, EN 61000-6-2/-6-4
-
EMI
- CISPR 32, FCC Part 15B Class A
-
EMS
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
IEC 61000-4-3 RS: 5100 MHz to 6000 MHz: 3 V/m
IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV
IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
-
Railway
- EN 50121-4, EN 50155
-
Safety
- UL 508
-
Shock
- IEC 60068-2-27
-
Vibration
- IEC 60068-2-6
MTBF
-
Time
- 1,358,656 hrs
-
Standards
- Telcordia SR332
Warranty