Universal controller, 8 AIs, 2 AOs, Click&Go, -10 to 60°C operating temperature
Input/Output Interface
-
Analog Input Channels
-
Analog Output Channels
-
Buttons
-
Isolation
-
Rotary Switch
Analog Inputs
-
Accuracy
- ±0.1% FSR @ 25°C
±0.3% FSR @ -10 to 60°C
-
Connector
- Screw-fastened Euroblock terminal
-
I/O Mode
-
I/O Type
-
Input Impedance
-
Input Range
- ±150 mV
±500 mV
±5 V
±10 V
0 to 20 mA
4 to 20 mA
-
Resolution
-
Sampling Rate
- All Channels: 10 samples/sec for voltage; 6 samples/sec for current
Per Channel: 1.25 samples/sec for voltage; 0.75 samples/sec for current
Single channel: 1.25 samples/sec for voltage; 0.75 samples/sec for current
-
Built-in Resistor for Current Input
Analog Outputs
-
Accuracy
- ±0.1% FSR @ 25°C
±0.3% FSR @ -10 to 60°C
-
Output Range
-
Resolution
-
Load (Current Mode)
- Internal power: 250 ohms (max.)
LED Interface
-
LED Indicators
- PWR, RDY, Serial, I/O Status
Ethernet Interface
-
10/100BaseT(X) Ports (RJ45 connector)
-
Magnetic Isolation Protection
Ethernet Software Features
-
Configuration Options
- Web Console (HTTP), Windows Utility (ioAdmin)
-
Industrial Protocols
- CGI commands, Modbus TCP Server (Slave), Moxa AOPC (Active Tag), MXIO Library, SNMPv1 Trap, SNMPv1/v2c/v3
-
Management
- BOOTP, IPv4, SMTP, DHCP Client, HTTP, TCP/IP
-
MIB
-
Time Management
Serial Interface
-
Connector
-
Serial Standards
-
No. of Ports
-
Baudrate
- 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
-
Parity
-
Data Bits
-
Stop Bits
-
Flow Control
Serial Software Features
-
Industrial Protocols
- Modbus RTU Server (Client)
Power Parameters
-
Power Connector
- Screw-fastened Euroblock terminal
-
No. of Power Inputs
-
Input Voltage
-
Power Consumption
Physical Characteristics
-
Dimensions
- 115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in)
-
Weight
-
Installation
- DIN-rail mounting, Wall mounting
-
Wiring
- I/O cable, 16 to 26 AWG
Power cable, 16 to 26 AWG
-
Housing
Environmental Limits
-
Operating Temperature
- -10 to 60°C (14 to 140°F)
-
Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
-
Ambient Relative Humidity
- 5 to 95% (non-condensing)
-
Altitude
Standards and Certifications
-
Freefall
-
EMC
-
Safety
-
EMI
- CISPR 32, FCC Part 15B Class A
-
EMS
- IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV
IEC 61000-4-5 Surge: Power: 1 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF
-
Shock
-
Vibration