ioPAC 85xx I/O module, 8 AIs, 0 to 10 V, -40 to 75C
Input/Output Interface
-
Analog Input Channels
-
Isolation
Analog Inputs
-
Accuracy
- ±0.1% FSR @ 25°C
±0.3% FSR @ -40 to 75°C
-
Connector
- Spring-type Euroblock terminal
-
I/O Type
-
Input Impedance
-
Input Range
-
Resolution
-
Sampling Rate
- All channels: 100 samples/sec
Per channel: 12.5 samples/sec
Physical Characteristics
-
Dimensions
- 25 x 128.2 x 85.5 mm (0.98 x 5.05 x 3.37 in)
-
Weight
-
Wiring
Environmental Limits
-
Operating Temperature
- -40 to 75°C (-40 to 167°F)
-
Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
-
Ambient Relative Humidity
- 5 to 95% (non-condensing)
-
Altitude
- 2000 m
Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
Standards and Certifications
-
EMC
- EN 55032/24
EN 61000-6-2/-6-4
-
EMI
- CISPR 32, FCC Part 15B Class A
-
EMS
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
IEC 61000-4-3 RS: 5100 MHz to 6000 MHz: 3 V/m
IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV
IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF
-
Railway
- EN 50121-4
EN 50155 (complies with a portion of EN 50155 specifications)
-
Safety
-
Shock
-
Vibration